Configuring report control block clients with IEC 61850 Configuration - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX640 Protection and control - Relion Protection and Control - PCL6 - IEC - ANSI - 14.02.2023

REX640 IEC 61850 Engineering Guide

Add and configure the IEDs before configuring the RCB client. The potential clients and their communication configuration should be known for a successful RCB client configuration.
  1. In Plant Structure, click the IED node which is the RCB server.
  2. Click the Report Controls tab.

    The rows of the Report Controls window show the RCBs configured for the IED.

    The columns of the Report Controls window show the RCB clients configured in the PCM600.

  3. To add or remove clients for an RCB, click the check box in the grid, corresponding to the client and RCB.

    Five clients at a maximum can be connected to an RCB.

    Figure 1. RCB clients
    image/svg+xml12
    1
    RCBs configured for the IED
    2
    RCB clients
Note: The clients are automatically added to or removed from the corresponding data sets on the Data Sets tab. Date sets are based on the configuration done on the Reports Controls tab and vice versa.