Inserting an IED in online mode - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Engineering Manual - REX640 Protection and control - PCL6 - IEC - ANSI

REX640 Engineering Manual

To set up an IED online, the protection relay must be connected to PCM600.

When the protection relay is connected to PCM600, PCM600 can read the composition code directly from the relay. It is possible to read the full configuration from the relay by using the Read from IED function.

  1. In the Plant Structure view, right-click the bay, point to New, point to the relay application area such as Multiapplication IEDs and select the protection relay type to be inserted.
    Tip: Alternatively, drag an IED from the Object Types view to the bay level.
    Figure 1. Selecting the protection relay type

  2. On the Configuration mode selection page, select Online Configuration and click Next.
    Figure 2. Selecting the configuration mode

  3. On the Communication protocol page, select the communication protocol from the IED Protocol list and click Next.
    Figure 3. Selecting the communication protocol

  4. On the IEC61850 communication protocol page, select the port from the Port list.
    • If the LAN port is selected, type the correct IP address (of the physical protection relay to be configured) to the IP address box. Use the either the front port which has default IP address 192.168.0.254 or Network 1 which has a factory default IP address 192.168.2.10
    Figure 4. Selecting the communication port and IP address

    Communication configuration is now defined.

  5. Click Next to scan/read the composition code of the protection relay.
  6. On the Composition code detection page, click Next.
    Figure 5. Detecting the composition code

  7. On the Configuration selection page, select the configuration type and click Next.
    • Select Empty Configuration to create an empty configuration.
    • Select Import configuration from file (APCMI/APCMT) to import any existing example configuration.

      Click Browse to select the .pcmi or .pcmt file that has the example configuration.

    Figure 6. Selecting the configuration type

  8. On the Version Selection page, select the IEC 61850 version and click Next.
    Figure 7. Selecting the IEC 61850 version

    Note: Regardless of the protocol used in the installation for each project, it is possible to have Edition1 and Edition2 relays configured in the same PCM600 project. The PCM600 project's SCL edition is the highest SCL edition relay in the project.
  9. On the Summary page, click Finish to confirm the configuration and insert the IED.

    The Summary page shows the protection relay's IED type, IP address and the selected composition code.

    Figure 8. Confirming the configuration

    Note: If an error is shown on the Summary page, it is not possible to go back and make modifications. If an error is detected, cancel the insertion by clicking Cancel and insert the IED again.