- Select an existing IED.
- From the Files of type list, select the IEC 61850 file type to be imported (ICD or CID).
-
In the SCL Import Option dialog box, select how the file is to be handled during the import.
Figure 1. SCL Import Options - Don't import protects the existing IEDs if the SCD file does not match the original configuration in PCM600.
- Replace unknown can be used when the file includes additional IEDs that are needed. The IED of type “Generic IEC 61850 IED” is used to integrate this kind of IEDs into, for example, the plant structure.
- Ignore PCM Object Type updates the IED objects in PCM600 from the IED types in the SCD file, whether or not the IED types in the SCD file match the IED objects in PM600.
- Ignore Substation Section does not import the SSD file part of the SCD file.
-
Click Import when the definition has been completed.
A progress view displays the importing procedure.