Function block execution parameters - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Engineering Manual - REX640 Protection and control - PCL6 - IEC - ANSI - 16.02.2023

REX640 Engineering Manual

Three function block execution parameters influence the runtime execution of the function block within the application configuration.

  • Execution order
  • Cycle time
  • Instance number

When a new function block is inserted, these parameters are shown in the Function Block Instance dialog box in Application Configuration. The three parameters are selectable or not selectable depending on the function block type. The cycle time is predefined to one value. The instance number is a counter for the total possible number of function blocks of that type used within the application configuration.

Execution Order and Instance Number are a combination that is predefined within a product. It is possible to select a pair out of the list.

Figure 1. Application Configuration tool: an example of function block organization parameters
image/svg+xml

Cycle Time is automatically set and it cannot be modified.

Tip: To automatically calculate the execution order, click Calculate Execution Order on the tool bar.