Exporting ICD or CID files - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Engineering Manual - REX640 Protection and control - PCL6 - IEC - ANSI - 16.02.2023

REX640 Engineering Manual

  1. Select the IED in the Plant Structure view.
  2. Right-click the IED and select Export.
  3. In the Export dialog box, from the Save as type list, select the type of file to export.
    • Configured IED description (.cid) for the IEC 61850 structure as needed for the IED at runtime
    • IED capability description (.icd) for the IEC 61850 structure
    Figure 1. IEC 61850: Selecting the IED file type for export
  4. Click Save.
  5. In the SCL Export Options dialog box, select the export options.
    Figure 2. IEC 61850: Selecting the export options
    image/svg+xml
  6. Click Advanced to change the SCL file version if required by the receiving configuration tool.
    Figure 3. Selecting the SCL file version
    image/svg+xml
  7. Click Export.