Configuring Alarm Annunciator page - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Engineering Manual - REX640 Protection and control - Relion Protection and Control - PCL6 - IEC - ANSI - 16.02.2023

REX640 Engineering Manual

  1. Open Page Organizer in Graphical Display Editor.
  2. Select Add Page… on Main Pages section.
  3. Select Blank Page from Templates section.
  4. Open Page Editor, and drag and drop Alarm Annunciator widget on the empty page.
  5. Select image/svg+xml in the lower-right corner of the alarm annunciator page to open function grouping editor.
  6. Select Add to create new group.
  7. Activate one of the created groups and select Local HMI/LEDx in the list of available functions.
  8. Select
    to add LED to alarm group.
    Figure 1. Function grouping editor and 4 configured groups

  9. Select Save to close the editor.
  10. Activate Short description area for one of the LEDs and type description that is always visible on the annunciator page.

    Description can be split on three lines.

    Figure 2. Editor for short description in the alarm annunciator page

  11. Activate Long description for one of the LEDs and type description that becomes visible when alarm is tapped on HMI page.
    Figure 3. Editor for long description in the alarm annunciator page