Communication between PCM600 and the protection relay - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Engineering Manual - REX640 Protection and control - PCL6 - IEC - ANSI - 16.02.2023

REX640 Engineering Manual

The communication between the protection relay and PCM600 is independent of the used communication protocol within the substation or to the NCC.

All communication is done over Ethernet using either IEC 61850 or the FTP/FTPS protocol.

When an Ethernet-based station protocol is used, the same Ethernet port and IP address can be used for PCM600 communication.

Two basic variants have to be considered for the connection between PCM600 and the protection relay.

  • Direct point-to-point link between PCM600 and service port X1.2 on the protection relay's LHMI or, if an LHMI is not used, the HMI port X0 of the communication module
  • Indirect link via station LAN or remotely via network
  1. If needed, the IP address for the protection relay is set.
  2. A PC or workstation is set up for a direct link (point-to-point), or the PC or workstation is connected to the LAN/WAN network.
  3. The protection relays' IP addresses in the PCM600 project are configured to match the IP addresses of the physical IEDs.
  4. Technical keys of the IEDs in the PCM600 project are configured to match the technical keys of the physical IEDs.

For successful protection relay engineering and usage, the workstation firewall TCP and UDP port configurations should be checked, especially for IEC 61850 and FTP. Other protocols are not used for engineering or they are optional.