Using the Web HMI - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - Operation Manual - REX615 Protection and control - Relion 615 series - PCL2 - IEC - ANSI - 01.04.2026

REX615 Operation Manual

WHMI is disabled by default, and has to be activated in the protection relay configuration. As secure communication is enabled by default, the WHMI must be accessed from a Web browser using the HTTPS protocol. Three simultaneous WHMI sessions are supported.

  1. To enable the WHMI, select Main menu > Configuration > HMI > Web HMI mode.
  2. Reboot the relay for the change to take effect.
  3. Log in with the proper user rights to use the WHMI.
Tip: To establish a remote WHMI connection to the protection relay, contact the network administrator to check the company rules for IP and remote connections.
Note: Disable the Web browser proxy settings or make an exception to the proxy rules to allow the protection relay's WHMI connection, for example, by including the relay's IP address in Internet Options > Connections > LAN Settings > Advanced > Exceptions.