Serial communication ports and drivers - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - Operation Manual - REX615 Protection and control - PCL2 - IEC - ANSI - 16.05.2023

REX615 Operation Manual

Depending on the hardware configuration, the protection relay can be equipped with one or several UART-based serial communication ports. The communication ports can be either galvanic (RS-485, RS-232) or fiber optic. The protection relay uses serial ports and drivers as different types of serial communication protocol links.

Serial ports are called COM1, COM2 and so on, depending on the number of serial ports in the relay hardware configuration. Each COM port driver has its own setting parameters found via the LHMI in Configuration > Communication > COMn (n= 1,2,…).

Since the same protection relay usually supports a variety of different communication hardware options, all COM port driver setting parameters are not relevant for every communication hardware type.

Table 1. COM port parameters in different HW options
COM parameter Values Hardware options
Fiber mode 0 = No fiber

Used in the fiber optic mode only.

Note that ”No fiber “ mode is the same as the galvanic mode.

1 = Fiber light ON/loop
2 = Fiber light OFF/loop
3 = Fiber light ON/star
4 = Fiber light OFF/star
Serial mode 0 = RS485 2wire

For galvanic modes. RS-type depends on the communication card used.

Note that this setting parameter is relevant only if Fiber mode is set to “No Fiber”.

1 = RS485 4wire
2 = RS232 no handshake
3 = RS232 with handshake
CTS Delay 0…60000 [ms] RS232 mode only
RTS Delay 0…60000 [ms] RS232 mode only
Baudrate 1 = 300 All modes
2 = 600
3 = 1200
4 = 2400
5 = 4800
6 = 9600
7 = 19200
8 = 38400
9 = 57600
10 = 115200 [bits/sec]
Note: In addition to setting the COM parameter, a communication card with many hardware options may also require changing the jumpers on the communication card.

Connection of a serial communication protocol to a specific serial port

The serial communication protocol (instance) settings include a setting parameter called Serial port n (n = protocol instance number). Setting options for this parameter are “COM1”, “COM2” and so on. The desired serial port for the protocol instance is selected through this parameter.

Note: All link setting parameters are not found in the COMn settings. Additional link setting parameters are found in the setting parameter list of the used serial protocol, since some serial protocol standards allow changes in link parameters, while other protocol standards do not.
1 When fiber mode is used, the Serial mode parameter value must be “RS485 2wire”.