Selecting local or remote use - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - Operation Manual - REX615 Protection and control - PCL2 - IEC - ANSI - 18.04.2024

REX615 Operation Manual

The control position of the protection relay can be changed with the R/L button. In local position primary equipment, such as circuit breakers or disconnectors, can be controlled via the LHMI. In remote position, control operations are possible only from a higher level, that is from a control center.

Press for two seconds.
  • When the L LED is lit, local control is enabled and remote control disabled.

  • When the R LED is lit, remote control is enabled and local control disabled.

  • When neither of the LEDs is lit, both control positions are disabled.

  • When the L and R LEDs are lit, both remote and local control are enabled.
Note: By default, the control position cannot be local and remote simultaneously. See the technical manual for more information on local and remote control.
Note: To control the protection relay, log in with the appropriate user rights.