Polled measurement data from Modbus Slaves - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - Modbus Communication Manual - REX615 Protection and control - PCL2 - IEC - ANSI - 30.09.2025

REX615 Modbus Master Communication Protocol Manual

Measurement data is located in Modbus 3X and 4X memory areas. The polled measured data is mapped to MMVI4GAPC and MMVF4GAPC functions data objects.

In CMT, the Readable register -type menu is to be selected.

The following parameters can be configured by the user:

Table 1. User-configurable parameters
Property Range Editable Description
Mapping 1 No Mapping number
Slave Number 1... 255 Yes Modbus Slave number for the request
Register Type 3 - 3x area Yes Modbus area where the requested value exists
4 - 4x area
Point Address 1... 65535 Yes Modbus data address

an empty address field disables the polling for that signal

Coding 1 ... 255 Yes How is the requested Modbus value coded:
1 - 16 bit integer
2 - 16 bit signed integer
3 - 32 bit integer
4 - 32 bit signed integer
5 - 32 bit integer Register swap
6 - 32 bit signed integer Register swap
7 - Float32 value
8 - Float32 value Register swap
9 ... 255 – expansion
Description ASCII 20 characters No 20 characters or less. This text is provided as an information field on the block and input in use
Group 0 ... 255 Yes 0 – Request is polled separately, no grouping
1... 255 – Request is polled among with other requests belonging to the same group number
Scale Any value Yes Scale factor applied to the value before storing to DA
Offset Any value Yes Offset applied to the value before storing to DA