SMVSENDER61869 (IEC 61869-9) ACT configuration and dataset editing - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX615 Protection and control - PCL2 - IEC - ANSI - 20.04.2026

REX615 IEC 61850 Engineering Guide

For IEC 61869-9 compliant SMV sending, the SMVSENDER61869 function block must be added to the ACT configuration.

When adding the function to ACT sheet, IEC 61869-9 compliant sampled value control block and related data set are automatically created. By default PCM600 tool creates PhsMeas2 data set and MSVCB03 control block, which are by default compliant to IEC 61869-9 svcb attributes, i.e. numOfASDU=2 and sampleRate=4800. It is recommended to only use the default template, as relay has limited support for any modifications on the control block attributes.