SMVRCVx ACT configuration - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX615 Protection and control - Relion Protection and Control - PCL2 - IEC - ANSI - 20.04.2026

REX615 IEC 61850 Engineering Guide

At least one SMVRCVx function block must be added to the ACT configuration of the SMV receiver protection relay to enable SMV receiving. One protection relay can have a maximum of four SMVRCVx blocks and up to 24 individual measurement channels.

Figure 1. SMVRCVx block in Application Configuration

Note: The SMVRCVx function block supports both IEC 61869-9 and 9-2LE profiles
Note: The SMVRCV’s decoder is configured based on Part 9-2 (2020; Edition 2.1), stating: All BER TLV Length fields shall be definite form, and encoded using the minimum size BER encoding possible. The relay will discard SV packets not conformant to this specification and UCA test case sSvp7.