SCL configuration checklist for ReportControl - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX615 Protection and control - Relion Protection and Control - PCL2 - IEC - ANSI

REX615 IEC 61850 Engineering Guide

The relay supports 20 data sets out of which four can be defined for GOOSE. For reporting, the total number of ReportControl blocks is 80 (//Services&/ConfReportControl/@max), which typically means that 16 report data sets can have five clients (//ReportControl/RptEnabled/@max). It may be easiest to replace the Services section by the section in the REX615 type data files.

Table 1. Possible errors if imported FPN SCD file contains invalid ReportControl blocks

Condition

Cause

Remedy

The customer IED contains one or more report control blocks having [xx] instantiated clients. The internal IED allows 5 instantiated report clients per report control block at maximum.

Some of the report controls have too many clients.

Check the report control blocks using IEC 61850 Configuration.

Too many reporting clients

Enabled clients are out of valid range for some of the report control blocks.

Using IEC 61850 Configuration, check the enabled clients from Object Properties for all the ReportControl blocks. This must be in the range of 2...5.