SCL configuration checklist for GOOSE - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX615 Protection and control - Relion Protection and Control - PCL2 - IEC - ANSI

REX615 IEC 61850 Engineering Guide

The relay supports six GOOSE send data sets so //SCL/IED/Services/GOOSE/ @max should not exceed 6. It may be easiest to replace the Services section by the section in the REX615 type data files.

In receiving, the relay uses APPID in packet detection. It is a standard way, however in some template projects, APPID is not set for send GOOSE. Variable //SCL/Communication/SubNetwork/ConnectedAP/GSE/Address/P/@type for APPID must be defined for each GSE element.

Table 1. Possible errors if imported FPN SCD file contains invalid GOOSE control blocks

Condition

Cause

Remedy

The customer IED contains [xx] GOOSE control blocks. The internal IED allows 6 GOOSE control blocks at maximum

There are too many GOOSE control blocks in the imported configuration.

Check the GOOSE control blocks using IEC 61850 Configuration.