In horizontal communication the user normally has to engineer IEC 61850-8-1 GOOSE data sets. When IEC 61850-9-2 is used, the connectivity package automatically creates a data set including data as defined in 9-2 LE: four currents and four voltages with quality attributes. If IEC 61869-9 is used for sampled values, then the data set must be manually configured.
It is not allowed to engineer or modify the predefined 9-2 LE data set. Together with the SMV data sets, the connectivity package also creates a default SMV control block. The SVCB configuration needs to be finalized in the tool before connecting the sent 9-2 LE or IEC 61869-9 data to the receiver IEDs.