FPN allows customer definition of the IEC 61850-8-1 data model. It is possible to have multiple logical devices and their data attribute tagging indicating functions and subfunctions.
Note: The test mode and setting group handling in the IED is global.
If the project contains functional naming, it is possible to have explicit LD name in /LD/@LDName attribute. Functional naming affects the MMS domain name and it changes the data set referencing objects of RCBs and GOOSE control blocks.
Note: Functional naming cannot be used for the relay's SMV model in MU01 because this is based on the IEC 61850-9-2 LE edition 1 specification.
Note: Functional naming can be used for the LD’s necessary subset.
PCM600 does not support functional naming configuration in an ABB-specific project, but it is possible to configure functional naming for the relay by importing the SCD project.