Functional naming - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX615 Protection and control - Relion Protection and Control - PCL2 - IEC - ANSI - 14.05.2025

REX615 IEC 61850 Engineering Guide

FPN allows customer definition of the IEC 61850-8-1 data model. It is possible to have multiple logical devices and their data attribute tagging indicating functions and subfunctions.

Note: The test mode and setting group handling in the IED is global.

If the project contains functional naming, it is possible to have explicit LD name in /LD/@LDName attribute. Functional naming affects the MMS domain name and it changes the data set referencing objects of RCBs and GOOSE control blocks.

Note: Functional naming cannot be used for the relay's SMV model in MU01 because this is based on the IEC 61850-9-2 LE edition 1 specification.
Note: Functional naming can be used for the LD’s necessary subset.

PCM600 does not support functional naming configuration in an ABB-specific project, but it is possible to configure functional naming for the relay by importing the SCD project.