Editing ReportControl blocks in IEC 61850 Configuration - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX615 Protection and control - Relion Protection and Control - PCL2 - IEC - ANSI

REX615 IEC 61850 Engineering Guide

To edit ReportControl blocks, IEC 61850 configuration engineering mode must be enabled from options.

Figure 1. Enabling IEC 61850 configuration engineering mode
  1. To open IEC 61850 Configuration, right-click an IED and select IEC 61850 Configuration.
    Figure 2. Opening IEC 61850 Configuration
    image/svg+xml
  2. On the toolbar, select Client-Server Communication from the drop-downmenu.
    Figure 3. Selecting client-server communication
  3. Click the Data Sets tab to edit data sets for report controls and the Report Controls tab to edit ReportControl blocks.
  4. To edit the clients for each ReportControl block, select a ReportControl block and open Clients from Object Properties.

One ReportControl block can have a maximum of five clients.