Diagnostic counters - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX615 Protection and control - Relion Protection and Control - PCL2 - IEC - ANSI

REX615 IEC 61850 Engineering Guide

The protection relays' IEC 61850 data model includes a logical node LD0.GSELPRT1 for the GOOSE communication diagnostic. The counters are also available via the HMI or PCM600 path Monitoring > I/O Status > Communication > GSELPRT1 > Monitoring.

It is possible to reset the GOOSE communication diagnostics counters via Monitoring > I/O Status > Communication > GSELPRT1 > Monitoring > Reset counters and via the IEC 61850 communication by writing TRUE to the CntRs.Oper.ctlVal attribute under GSELPRT1.

Table 1. Diagnostics data objects

Data object

Description

Diagnostic information

FrRxCnt

Received messages

When increasing, the protection relay is receiving GOOSE messages.

FrTxCnt

Transmitted messages

When increasing, the protection relay is sending GOOSE messages.

RxStCnt

Received state changes

Received GOOSE messages with a new stNum value

RxSeqCnt

Received sequence number

Received GOOSE retransmissions or heartbeat cycle messages with a new sequence number

RxTestCnt

Received frames with test bit

Received GOOSE frames with the test flag on. Incremented only in Edition 1 mode

StWrnCnt

State warnings

Number of detected state number jumps

SeqWrnCnt

Sequence warnings

Number of detected sequence number jumps

RxTmOutC nt

Receiver time-outs

Number of detected peer device time-outs

ConfErrCnt

Received ConfRev mismatches

When increasing, there is a mismatch between the received GOOSE frame information and configured GOOSE.

NdsComCnt

Received frames with Needs Commissioning bit

One or many peer devices indicate that their configuration is not valid or up-to-date.

DSErrCnt

Errors in received data set

Received data is syntactically incorrect, or the amount of data in the data set is not as expected.

Alm

Receiver alarm

Alarm signal value connected to the event and application logic. It is active when one or many peer devices are in time-out.

RptProtCnt

Replay protection warnings

Number of detected message replays

GOOSE Alarm is activated in the receiver device in certain situations.
  • Time-out
  • Configuration revision mismatch
  • Error in the received data set
  • The Needs Commissioning bit is active in the received message