Defining data set entries with IEC 61850 Configuration - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX615 Protection and control - PCL2 - IEC - ANSI

REX615 IEC 61850 Engineering Guide

  1. Select the Data Sets tab.
  2. Right-click a data set and select Details to add data attributes.
    Figure 1. Adding data attributes
  3. In the data set entry window, select the data attribute to be contained in the data set.
    • Click Append selected to add the data attribute to the end of the data set.
    • Click Insert selected to add the data attribute above the selected row in the data set entries list.
    • To remove a data attribute from the data set, select the data attribute in the data set entries pane and click Remove selected.

Reporting data sets can include status and measurement type of data. Also configuration and setting values can be added to data sets in case required.

Note: Data set entries for vertical reporting are selected using the data object level, and entries for GOOSE are selected using the data attribute or data object level.