Defining GOOSE data set entries with IEC 61850 Configuration - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX615 Protection and control - Relion Protection and Control - PCL2 - IEC - ANSI - 14.05.2025

REX615 IEC 61850 Engineering Guide

  1. Select the Data Sets tab.
  2. Right-click a data set and select Details to add data attributes.
  3. In the Data Set Entry window, select the data attribute or data object present in the data set.
    • Click Append selected to add the data to the end of the data set. To add a data object level entry, select it from the FC section. To add a data attribute level entry, select it from the DA section
    • Click Insert selected to add the data above the selected row in the data set entries list.
    • To remove a data from the data set, select the data in the data set entries pane and click Remove selected.
Figure 1. Adding data set entries
Note: If a data set has quality attributes, the attributes must be located after the status value of the same data object.

After defining the data entries for the data sets, configure the GOOSE control block properties.