Creating report control blocks with IEC 61850 Configuration - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX615 Protection and control - PCL2 - IEC - ANSI - 14.05.2025

REX615 IEC 61850 Engineering Guide

  1. Select the IED node in Plant Structure in Project Explorer.
  2. Click the Report Controls tab.
  3. Right-click the area containing the existing RCBs and select New to add a new RCB.
    Figure 1. Adding a new report control block
  4. Browse to LLN0 under LD0 to define where to place the RCB.
  5. Give a unique name to the RCB.
  6. In the drop-down list, select the previously created data set to link with the RCB.
    Figure 2. Selecting a data set to be linked with the RCB
  7. Edit the properties and options of the created RCB.
    Figure 3. Editing the RCB properties
Note: Data set entries in a data set linked to the GCB can be modified from the RCB Control Block tab by selecting the Data Set Details in the shortcut menu.