Control model - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX615 Protection and control - Relion Protection and Control - PCL2 - IEC - ANSI - 14.02.2023

REX615 IEC 61850 Engineering Guide

The product-specific default data model members are visible in parameter tables and details of function features can be found in the technical manual.

It is possible to use the customer data model, but the control model (ctlModel) allows only product-dependent choices. The control model can be status-only or direct-with-normal-security. For DPC, sbo-with-enhanced-security is also supported. The engineer can map the control model directly to the product data object or restrict the FPN model's default value to "status-only".

Time-activated control is not supported, but if the controllable objects contain additional optional attributes, it is possible to write the command structures. Optional attributes must then have default values.