Connecting sender function block signal to GOOSE receiver block using Application Configuration tab - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX615 Protection and control - Relion Protection and Control - PCL2 - IEC - ANSI

REX615 IEC 61850 Engineering Guide

  1. On the Application Configuration tab, select the sender IED function block signal and click Connect.
    Figure 1. Connecting non-directional earth-fault protection start signal

    The needed horizontal communication function block and input variable are created automatically.

    Tip: It is also possible to create the GOOSE receiver function block separately and connect it to the receiver and sender function block signals.
  2. Right-click the created input connection variable to navigate to the connected sender function block signal.
    Figure 2. Navigating to the connected sender function block signal