Connecting GOOSE inputs to a relay application - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX615 Protection and control - Relion Protection and Control - PCL2 - IEC - ANSI

REX615 IEC 61850 Engineering Guide

  1. In PCM600, open Project Explorer and select the Plant Structure tab.
  2. Add the GOOSERCV function block with Application Configuration.
    Note: The GOOSERCV function block can only be added with Application Configuration.
    Tip: Give the GOOSERCV block application-specific user-defined names to distinguish between different blocks when making GOOSE connections in Signal Matrix.
    Figure 1. Adding the GOOSERCV function block
    image/svg+xml
  3. Create the connection in the application.
    1. Create the connection.
    2. Save the connection to the application.
  4. To open Signal Matrix, right-click the protection relay, and select Signal Matrix.
  5. To map the input points to the receiving input data, click the cell.
    To expand the source field, drag the edge of the field to expand it until the whole GOOSE source address is visible.
  6. In Signal Matrix on the GOOSE tab, map the GOOSE publisher data to the corresponding GOOSERCV function block.
    The columns on the GOOSE tab represent publisher data and the rows represent the possible subscriber input points.
    Figure 2. GOOSE tab in Signal Matrix
    Note: The GOOSE receiver block output VALID defines the validity for the received data. The value is based on the received quality attribute value or communication status. This validity information can be used in the application to build the validity logic in addition to the GOOSE default supervision information.
    Note: During the protection relay start-up phase, the protection relay keeps the value of the output VALID as "1" (GOOD) until the communication is activated. After the communication is activated, the value of the output VALID is updated by the value received via the communication. If the quality attribute is missing from the received GOOSE data set, the GOOSE receiver block output VALID is always "1" (GOOD).
    Note: If the data type does not match with the GOOSERCV function block, the attribute cell is red.

    In Signal Matrix, the received GOOSE data can be directly connected to the relay application. The GOOSE inputs are shown on the Binary or Analog Inputs sheets and they can be connected to the application receiver function blocks. The columns represent publisher data and the rows represent the possible subscriber input points.

    If the data type, for example timestamp, is not supported by the relay application, the attribute column is red. The quality attribute is automatically incorporated in the application with the status value, and it is not seen in Signal Matrix.

  7. Save the changes made in Signal Matrix.
  8. Write to the IED.