Configuring a GOOSE control block with IEC 61850 Configuration - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX615 Protection and control - Relion Protection and Control - PCL2 - IEC - ANSI

REX615 IEC 61850 Engineering Guide

  1. Select the IED in the Plant Structure view.
  2. Select the GOOSE Controls tab in the tool pane.
  3. To add a new GOOSE control block, right-click the area containing the existing GOOSE control blocks and select New.
    Figure 1. Creating a new GOOSE control block
  4. Browse to LLN0 under LD0 to define where the GOOSE control block must be placed.
  5. Give a unique name to the GOOSE control block.
    Figure 2. Naming a GOOSE control block
  6. In the Data set drop-down list, select the previously created data set to link with the GCB.
    Figure 3. Data set drop-down list
    Note: Data set entries in a data set linked to the GCB can be modified from the GOOSE control block tab by selecting Data Set details in the shortcut menu.
  7. Edit the properties and addresses of the created GOOSE control block.

    Edit at least MAC Address and App ID.

    Figure 4. GOOSE control block properties
Note: With this protection relay, only Max Time is configurable, not Min Time.
Note: The multicast MAC Address is usually unique, and App ID must be unique. System SCL data validation is performed by PCM600 to check any overlapping APP IDs.