- In the Plant Structure view, right-click the correct sender IED and select IEC 61850 Configuration.
-
Select Process Bus Communication in the drop-down box on the toolbar.
Figure 1. Selecting Process Bus Communication The SMV sender and the possible SMV receiver IEDs become visible. -
On the Sampled Value Controls tab, edit the properties and addresses of the sampled value control block.
Figure 2. Changing the VLAN ID CAUTION: Some switches do not support multicast filtering with VLAN value “0” because it means “no VLAN” and VLAN 1 has a special purpose as the management VLAN for switches. The recommended value for VLAN is 2...1001.Note: Use a unique multicast address for each SVCB. The address range for sampled values multicast addresses is 01-0C-CD-04-00-00...01-0C-CD-04-01-FF.Note: Selected IEC 61850 edition is followed by default. Samples Synchronized behavior can be controlled using Smv SmpSynch format parameter in SMVSENDER function. - Connect the SMV sender to the receivers.
-
In PCM600, select Write to IED.
Figure 3. Configuring the SMV sender and receivers Note: If the configuration is updated in a manner that affects the SV frame content, e.g. options, SVID, Conf.Rev , dst MAC change, configurations of both SMV sender and all receivers must be rewritten from PCM600 to the relays.