Configuring SMV with IEC 61850 Configuration - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX615 Protection and control - Relion Protection and Control - PCL2 - IEC - ANSI

REX615 IEC 61850 Engineering Guide

The connection between the SMV sender and receiver is handled using IEC 61850 Configuration.
  1. In the Plant Structure view, right-click the correct sender IED and select IEC 61850 Configuration.
  2. Select Process Bus Communication in the drop-down box on the toolbar.
    Figure 1. Selecting Process Bus Communication
    The SMV sender and the possible SMV receiver IEDs become visible.
  3. On the Sampled Value Controls tab, edit the properties and addresses of the sampled value control block.
    Figure 2. Changing the VLAN ID
    CAUTION: Some switches do not support multicast filtering with VLAN value “0” because it means “no VLAN” and VLAN 1 has a special purpose as the management VLAN for switches. The recommended value for VLAN is 2...1001.
    Note: Use a unique multicast address for each SVCB. The address range for sampled values multicast addresses is 01-0C-CD-04-00-00...01-0C-CD-04-01-FF.
    Note: Selected IEC 61850 edition is followed by default. Samples Synchronized behavior can be controlled using Smv SmpSynch format parameter in SMVSENDER function.
  4. Connect the SMV sender to the receivers.
  5. In PCM600, select Write to IED.
    Figure 3. Configuring the SMV sender and receivers
    Note: If the configuration is updated in a manner that affects the SV frame content, e.g. options, SVID, Conf.Rev , dst MAC change, configurations of both SMV sender and all receivers must be rewritten from PCM600 to the relays.