Configuring SMV receiver with Signal Matrix’s SMV tool - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX615 Protection and control - Relion Protection and Control - PCL2 - IEC - ANSI

REX615 IEC 61850 Engineering Guide

The connection between the SMV receiver and sender is handled using the Signal Matrix’s SMV tool. If the receiver IED’s ACT configuration includes multiple SMVRCVx blocks, the SMV tool can also be used to specify which sender is connected to which receiver.

  1. In the Plant Structure view, right-click the correct receiver IED and select Signal Matrix.
  2. Select the SMV tab.
  3. Connect the SMV receiver with the sender.
    Figure 1. Configuring the SMV receiver
    Figure 2. Configuring the SMV receiver in case of multiple SMVRCVx blocks

    After saving in Signal Matrix tool the outputs of the SMV receiver block in ACT are named according to the data set signals of the sender.