The connection between the SMV receiver and sender is handled using the Signal Matrix’s SMV tool. If the receiver IED’s ACT configuration includes multiple SMVRCVx blocks, the SMV tool can also be used to specify which sender is connected to which receiver.
In the Plant Structure view, right-click the correct receiver IED and select Signal Matrix.
Select the SMV tab.
Connect the SMV receiver with the sender.
Figure 1. Configuring the SMV receiverFigure 2. Configuring the SMV receiver in case of multiple SMVRCVx blocks
After saving in Signal Matrix tool the outputs of the SMV receiver block in ACT are named according to the data set signals of the sender.