Sampled measured values and IEEE 1588 v2 time synchronization - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX615 Protection and control - Relion Protection and Control - PCL1 - IEC - ANSI - 22.04.2024

REX615 IEC 61850 Engineering Guide

The protection relay supports the IEC 61850 process bus with the IEC 61850-9-2 sampled values protocol. By default, if sampled values sending is enabled, relay sends 9-2LE conformant sampled values data. However, if modifying specific SMV options or attributes, the SMV data might not be according to 9-2LE specification anymore. PCM600 gives user a warning if the SMV stream configured is not according to 9-2LE. If SMV data is sent to e.g. 3rd party device, system engineer must ensure is the SMV receiving device is capable to e.g. handle specific SMV options.