The SMVSENDER function block must be added to the ACT configuration and connected to at least one triplet or residual channel to activate SMV sending. Unused channels in SMVSENDER must be connected to GRPOFF. As a result, the sampled value control block and the related data set are automatically added to the protection relay configuration. Relay supports sample rate of 4000 samples per second in a 50 Hz system and 4800 samples per second in a 60 Hz system.
CAUTION: Scaling of SMV currents is standardized to 1 mA/bit (IEC 61850-9-2LE and IEC 61869-9). In the case of calculated I0 (-3I0) the measured value can exceed the maximum 32 bit number reserved for measurements in IEC 61850-9-2. If the calculated I0 value exceeds 1518,5 kA RMS it will saturate (clip).
REX615 however also calculates the I0 from individual phase current when received over SMV, using this calculated I0 instead (ILTCTR IRES_CLK output) is a possible workaround.
Additionally when sending calculated I0 over SMV the maximum usable primary current setting is 11,8 kA in the sender IED. Exceeding this setting value results in zero amplitude for calculated I0 in SMV stream. Workaround for this is also to use calculated I0 in calculated in receiver instead (ILTCTR IRES_CLK output).