SMVRCVx ACT configuration - Arc protection - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Grid automation - Busbar differential protection (high impedance) - Line differential protection - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX615 Protection and control - Relion Protection and Control - PCL1 - IEC - ANSI - 22.04.2024

REX615 IEC 61850 Engineering Guide

At least one SMVRCVx function block must be added to the ACT configuration of the SMV receiver protection relay to enable SMV receiving.

A maximum of 16 SMV channels can be received The total number of channels that the relay can process is 64 including local, remote and calculated channels. Forwarding of received SMV channels through SMVSENDER is not supported.
Figure 1. SMVRCVx block in Application Configuration