The IEC 61850 data model can include up to four logical devices where different logical nodes, representing protection and control functionality, are located. Depending on the selected functionality in the protection relay, different configurations have different sets of logical devices and logical nodes. Data models also include modelling and functionality of settings, setting groups and configuration according to the IEC 61850 concept.
- Control logical device, CTRL
- Disturbance recorder logical device, DR
- Protection logical device, LD0
- Sampled measured values sending logical device, MU01, if configured
All generic functionality, such as modelling of physical inputs and outputs as well as the alarming LED functionality, resides under logical device LD0. A full description of the protection relay's data model is available in the parameter list.
The data model can be exported from PCM600 to an SCL file.