In case of a warning, the protection relay continues to operate except for those protection functions possibly affected by the fault, and the green Ready LED remains lit as during normal operation.
Warnings are indicated with the text Warning additionally provided with the name of the warning, a numeric code and the date and time on the LHMI. The warning indication message can be manually cleared.
The display code format for the warning codes is aa.bb.cc.ddd.ee.
- aa: Reserved for future
-
bb: Error domain
- 1: HW error
- 2: Runtime error
- 3: Communication error
-
cc: Component
- Range 0...11
- ddd: Warning category
-
ee: Offset
- Range 0...255
Warning indication |
Warning category |
Additional information |
---|---|---|
System |
2 |
Error in file operations |
Watchdog reset |
10 |
Watch dog reset has occurred |
Power down det. |
11 |
Auxiliary supply voltage dropped too low |
Modbus warning |
21 |
Error in Modbus communication |
Dataset error |
24 |
Error in data set(s) |
Report cont. Error |
25 1 |
IEC report error |
SCL config error |
27 |
Error in SCL configuration file or the file is missing |
Logic warning |
28 |
Too many connections in the configuration |
SMT connect error |
29 |
Error in SMT connections |
GOOSE input warning |
30 1 |
Error in GOOSE connections |
ACT Config. mismatch |
37 |
Configuration mismatch |
SDcard mount Warn |
156 |
SD card mount error |
ARC data invalid |
159 |
ARC traceability warning |
PSU.data.invalid |
160 1 |
PSU traceability warning |
DIO.data.invalid |
161 1 |
DIO traceability warning |
AIU.data.invalid |
162 1 |
AIU traceability warning |
AIC.data.invalid |
163 1 |
AIC traceability warning |
HMI.data.invalid |
164 1 |
HMI traceability warning |
LHMI keyscan error |
169 1 |
Keyscan error |
GOOSE receive error |
170 |
Error in GOOSE message receiving |
GOOSE publish error |
171 1 |
Error in GOOSE publish |
SDcard memory full |
172 |
SD card memory is full |
Device Cert. Expired |
173 |
Device certificate expired |
SDcard error |
174 |
Error in SD card |
SNTP error |
175 |
Error in the SNTP module |
Internal voltage error |
176 1 |
Voltage error detected |
Inter. humidity sensor error |
177 |
Error in internal humidity sensor |
Inter. temp. sensor error |
178 |
Error in internal temperature sensor |
Access Errx |
179 |
Setting write failure |
Config. not available |
181 |
Error in ACT connections/ACT Configuration not available |
SCL validation warning |
182 |
Failure in SCL file validation |
MMS report warning |
183 1 |
MMS report warning |
MMS service warning |
184 1 |
MMS service warning |
For further information on warning indications, see the operation manual.