Warnings - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - IEC - ANSI - 03.05.2023

REX610 Technical Manual

In case of a warning, the protection relay continues to operate except for those protection functions possibly affected by the fault, and the green Ready LED remains lit as during normal operation.

Warnings are indicated with the text Warning additionally provided with the name of the warning, a numeric code and the date and time on the LHMI. The warning indication message can be manually cleared.

Note: If a warning appears, record the name and code so that it can be provided to ABB customer service.

The display code format for the warning codes is aa.bb.cc.ddd.ee.

  • aa: Reserved for future
  • bb: Error domain
    • 1: HW error
    • 2: Runtime error
    • 3: Communication error
  • cc: Component
    • Range 0...11
  • ddd: Warning category
  • ee: Offset
    • Range 0...255
Figure 1. Warning
image/svg+xml
Table 1. Warning indications and codes

Warning indication

Warning category

Additional information

System

2

Error in file operations

Watchdog reset

10

Watch dog reset has occurred

Power down det.

11

Auxiliary supply voltage dropped too low

Modbus warning

21

Error in Modbus communication

Dataset error

24

Error in data set(s)

Report cont. Error

25 1

IEC report error

SCL config error

27

Error in SCL configuration file or the file is missing

Logic warning

28

Too many connections in the configuration

SMT connect error

29

Error in SMT connections

GOOSE input warning

30 1

Error in GOOSE connections

ACT Config. mismatch

37

Configuration mismatch

SDcard mount Warn

156

SD card mount error

ARC data invalid

159

ARC traceability warning

PSU.data.invalid

160 1

PSU traceability warning

DIO.data.invalid

161 1

DIO traceability warning

AIU.data.invalid

162 1

AIU traceability warning

AIC.data.invalid

163 1

AIC traceability warning

HMI.data.invalid

164 1

HMI traceability warning

LHMI keyscan error

169 1

Keyscan error

GOOSE receive error

170

Error in GOOSE message receiving

GOOSE publish error

171 1

Error in GOOSE publish

SDcard memory full

172

SD card memory is full

Device Cert. Expired

173

Device certificate expired

SDcard error

174

Error in SD card

SNTP error

175

Error in the SNTP module

Internal voltage error

176 1

Voltage error detected

Inter. humidity sensor error

177

Error in internal humidity sensor

Inter. temp. sensor error

178

Error in internal temperature sensor

Access Errx

179

Setting write failure

Config. not available

181

Error in ACT connections/ACT Configuration not available

SCL validation warning

182

Failure in SCL file validation

MMS report warning

183 1

MMS report warning

MMS service warning

184 1

MMS service warning

For further information on warning indications, see the operation manual.

1 Used for software simulation