Table 1. PHxPTOC Technical data

Characteristic

Value

Operation accuracy

PHLPTOC

Depending on the frequency of current measured: fn ±2 Hz

±1.5% of the set value or ±0.002 × In 1

±1.5% of the set value or ±0.007 × In 2

PHHPTOC

and PHIPTOC

±1.5% of the set value or ±0.002 × In 1

±1.5% of the set value or ±0.007 × In 2

(at currents in the range of 0.1…10 × In)

±5% of the set value

(at currents in the range of 10…40 × In)

Start time 3, 4

PHIPTOC:

IFault = 2 × set Start value

IFault = 10 × set Start value

Minimum

Typical

Maximum

12ms

8 ms

20 ms

13 ms

38 ms

31 ms

PHHPTOC and PHLPTOC:

IFault = 2 × set Start value

25 ms

35 ms

48 ms

Reset time

Typically 40 ms

Reset ratio

Typically 0.96

Retardation time

<45 ms

Operate time accuracy in definite time mode

±1.0% of the set value or ±40 ms

Operate time accuracy in inverse time mode

±5.0% of the theoretical value or ±50 ms 5

Suppression of harmonics

RMS: No suppression

DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

Peak-to-Peak: No suppression

P-to-P+backup: No suppression

1 Measurement mode = "RMS", "DFT" and "Peak-Peak" mode with CT secondary >0.2 A
2 Measurement mode = "Peak-to-peak", CT Secondary <0.2 A
3 Measurement mode = default (depends on the stage), current before fault = 0.0 × In, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
4 Includes the delay of the signal output contact (SO)
5 Maximum Start value = 2.5 × In, Start value multiples in the range of 1.5...20