Table 1. EFxPTOC Technical data

Characteristic

Value

Operation accuracy

EFLPTOC

Depending on the frequency of the current measured: fn ±2 Hz

±1.5% of the set value or ±0.002 × In

EFHPTOC

and EFIPTOC

±1.5% of the set value or ±0.002 × In

(at currents in the range of 0.1…10 × In)

±5.0% of the set value

(at currents in the range of 10…40 × In)

Start time 1, 2

EFIPTOC:

IFault = 2 × set Start value

IFault = 10 × set Start value

Minimum

Typical

Maximum

22 ms

13 ms

27 ms

18 ms

37 ms

34 ms

EFHPTOC and EFLPTOC:

IFault = 2 × set Start value

20 ms

30 ms

42 ms

Reset time

Typically 40 ms

Reset ratio

Typically 0.96

Retardation time

<45 ms

Operate time accuracy in definite time mode

±1.0% of the set value or ±40 ms

Operate time accuracy in inverse time mode

±5.0% of the theoretical value or ±50 ms 3

Suppression of harmonics

RMS: No suppression

DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

Peak-to-Peak: No suppression

1 Measurement mode = default (depends on the stage), current before fault = 0.0 × In, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2 Includes the delay of the signal output contact (SO)
3 Maximum Start value = 2.5 × In, Start value multiples in the range of 1.5...20