Characteristic | Value | |||
---|---|---|---|---|
Operation accuracy | Depending on the frequency of the measured voltage: fn ±2 Hz | |||
±1.5% of the set value or ±0.002 × Un | ||||
Start time 1, 2 |
UFault = 0.99 × set Start value UFault = 0.9 × set Start value |
Minimum | Typical | Maximum |
50 ms 41 ms |
60 ms 51 ms |
70 ms 61 ms |
||
Reset time | Typically 40 ms | |||
Reset ratio | Depends on the set Relative hysteresis | |||
Retardation time | <45 ms | |||
Operate time accuracy in definite time mode | ±1.0% of the set value or ±40 ms | |||
Suppression of harmonics | DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,… |
1 Start value = 1.0 × Un, Voltage before fault = 1.1 × Un, fn = 50 Hz, undervoltage in one phase-to phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2 Includes the delay of the signal output contact