Technical data - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - 1.2 - IEC - ANSI - 03.05.2023

REX610 Technical Manual

Table 1. PSPTUV Technical data
Characteristic Value
Operation accuracy Depending on the frequency of the measured voltage: fn ±2 Hz
±1.5% of the set value or ±0.002 × Un
Start time 1, 2

UFault = 0.99 × set Start value

UFault = 0.9 × set Start value

Minimum Typical Maximum

50 ms

41 ms

60 ms

51 ms

70 ms

61 ms

Reset time Typically 40 ms
Reset ratio Depends on the set Relative hysteresis
Retardation time <45 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±40 ms
Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
1 Start value = 1.0 × Un, Voltage before fault = 1.1 × Un, fn = 50 Hz, undervoltage in one phase-to phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2 Includes the delay of the signal output contact