Technical data - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - 1.2 - IEC - ANSI - 03.05.2023

REX610 Technical Manual

Table 1. NSPTOV Technical data
Characteristic Value
Operation accuracy Depending on the frequency of the voltage measured: fn
±1.5% of the set value or ±0.002 × Un
Start time1, 2

UFault = 1.1 × set Start value

UFault = 2.0 × set Start value

Minimum Typical Maximum

30 ms

20 ms

41 ms

32 ms

52 ms

43 ms

Reset time Typically 40 ms
Reset ratio Typically 0.96
Retardation time <45 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±40 ms
Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
1 Negative-sequence voltage before fault = 0.0 × Un, fn = 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2 Includes the delay of the signal output contact