Characteristic | Value | |||
---|---|---|---|---|
Operation accuracy | Depending on the frequency of the measured voltage: f/f n = ±2 Hz | |||
±0.6 % or ±0.002 × U n |
||||
Suppression of harmonics |
DFT: -50 dB at f = n × f n, where n = 2, 3, 4, 5,… RMS: No suppression |