Technical data - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - 1.2 - IEC - ANSI - 19.09.2022

REX610 Technical Manual

Table 1. PHPTUV Technical data
Characteristic Value
Operation accuracy Depending on the frequency of the measured voltage: f n ±2 Hz
±1.5% of the set value or ±0.002 × U n
Start time , U Fault = 0.9 × set Start value Minimum Typical Maximum
58 ms

70 ms

82 ms

Reset time Typically 40 ms
Reset ratio Depends on the set Relative hysteresis
Retardation time <45 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±40 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±50 ms
Suppression of harmonics DFT: -50 dB at f = n × f n, where n = 2, 3, 4, 5,…
1 Start value = 1.0 × U n, Voltage before fault = 1.1 × U n, f n = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2 Includes the delay of the signal output contact
3 Minimum Start value = 0.50, Start value multiples in range of 0.90...0.20