Table 1. CSMSQI Technical data
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: fn = ±2 Hz

±1.0 % or ±0.002 × I n

at currents in the range of 0.01...4.00 × I n

Suppression of harmonics

DFT: -50 dB at f = n × f n, where n = 2, 3, 4, 5,…