Technical data - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - IEC - ANSI - 19.09.2022

REX610 Technical Manual

Table 1. PHPTUC Technical data
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: fn ±2 Hz
±1.5% of the set value or ± 0.002 × In
Start time Typically <65 ms
Reset time Typically <40 ms
Reset ratio Typically 1.04
Retardation time <45 ms
Operate time accuracy in definite time mode mode ±1.0% of the set value or ±40 ms