Technical data - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - 1.2 - IEC - ANSI - 19.09.2022

REX610 Technical Manual

Table 1. DEFxPDEF Technical data

Characteristic

Value

Operation accuracy

DEFLPDEF

Depending on the frequency of the measured current: fn ±2 Hz

Current:

±1.5% of the set value or ±0.002 × In Voltage:

±1.5% of the set value or ±0.002 × Un

Phase angle:

±2°

DEFHPDEF

Current:

±1.5% of the set value or ±0.002 × In

(at currents in the range of 0.1…10 × In)

±5.0% of the set value

(at currents in the range of 10…40 × In) Voltage:

±1.5% of the set value or ±0.002 × Un

Phase angle:

±2°

Start time 1, 2

Minimum

Typical

Maximum

DEFHPDEF

IFault = 2 × set Start value

36 ms

50 ms

88 ms

DEFLPDEF

IFault = 2 × set Start value

40 ms

50 ms

73 ms

Reset time

Typically 40 ms

Reset ratio

Typically 0.96

Retardation time

<45 ms

Operate time accuracy in definite time mode

±1.0% of the set value or ±40 ms

Operate time accuracy in inverse time mode

±5.0% of the theoretical value or ±50 ms 3

Suppression of harmonics

DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1 Measurement mode = default (depends on the stage), current before fault = 0.0 × In, fn = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2 Includes the delay of the signal output contact
3 Maximum Start value = 2.5 × In, Start value multiples in range of 1.5...20