Characteristic |
Value |
|||
---|---|---|---|---|
Operation accuracy |
DEFLPDEF |
Depending on the frequency of the measured current: fn ±2 Hz |
||
Current: ±1.5% of the set value or ±0.002 × In Voltage: ±1.5% of the set value or ±0.002 × Un Phase angle: ±2° |
||||
DEFHPDEF |
Current: ±1.5% of the set value or ±0.002 × In (at currents in the range of 0.1…10 × In) ±5.0% of the set value (at currents in the range of 10…40 × In) Voltage: ±1.5% of the set value or ±0.002 × Un Phase angle: ±2° |
|||
Minimum |
Typical |
Maximum |
||
DEFHPDEF IFault = 2 × set Start value |
36 ms |
50 ms |
88 ms |
|
DEFLPDEF IFault = 2 × set Start value |
40 ms |
50 ms |
73 ms |
|
Reset time |
Typically 40 ms |
|||
Reset ratio |
Typically 0.96 |
|||
Retardation time |
<45 ms |
|||
Operate time accuracy in definite time mode |
±1.0% of the set value or ±40 ms |
|||
Operate time accuracy in inverse time mode |
±5.0% of the theoretical value or ±50 ms 3 |
|||
Suppression of harmonics |
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,… |
1 Measurement mode = default (depends on the stage), current before fault = 0.0 × In, fn = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2 Includes the delay of the signal output contact
3 Maximum Start value = 2.5 × In, Start value multiples in range of 1.5...20