Description |
Value |
|
---|---|---|
Width |
Frame |
149.5 mm (5.8858 in) |
Case |
127.5 mm (5.0196 in) |
|
Height |
Frame |
159.5 mm (6.2795 in) |
Case |
155.5 mm (6.1220 in) |
|
Depth |
202.8 mm (163.6 mm + 39.2 mm) (7.9842 in) |
|
Weight |
Protection relay with the four separate connectors |
2.5 kg (5.5 lbs) |
Description |
Value |
---|---|
Nominal auxiliary voltage Un |
24...250 48...240 ~ (V AC) |
Maximum interruption time in the auxiliary DC voltage without resetting the relay |
50 ms at Un |
Auxiliary voltage variation |
85...110% (AC) |
80...120% (DC) |
|
Start-up threshold |
Un (minimum) |
Burden of auxiliary voltage supply under quiescent (Pq)/operating condition |
9 W (Pq) 19 W/40 VA (Pmax) |
Ripple in the DC auxiliary voltage |
<15% |
Fuse type |
4A 250 ~ (V AC) fast (+UL DC rated) |
Description |
Value |
|
---|---|---|
Rated frequency |
50/60 Hz |
|
Current inputs |
Rated current, In |
1 A / 5 A |
Thermal withstand: Continuous |
20 A |
|
Thermal withstand For 1 s |
500 A |
|
Dynamic current withstand Half sine wave |
1250 A |
|
Input impedance |
<5 mΩ |
|
Voltage inputs |
Rated voltage |
57...250 ~ (V AC) |
Voltage withstand Continuous |
500 ~ (V AC) |
|
Voltage withstand For 10 s |
750 ~ (V AC) |
|
Burden at rated voltage |
<0.5 VA |
Description |
Value |
---|---|
Operating range |
24...250 |
48...240 ~ (V AC) |
|
Rated voltage |
80...120% (DC) |
85...110% (AC) |
|
Current drain |
Typically 1.6...1.9 mA <2.5 mA |
Power consumption |
<0.5 W |
Threshold voltage, pick-up |
Programmable 18...176 38...168 ~ (V AC) |
Threshold voltage, drop-off |
Programmable 16...176 34...168 ~ (V AC) |
Burden |
<0.5 W / 2 VA |
Description |
Value |
|
---|---|---|
Rated voltage |
250 V AC/DC |
|
Continuous contact carry current |
5 A |
|
Mechanical endurance |
Unloaded operation |
10000 cycles |
Electrical endurance |
Closing operations |
1000 cycles |
Opening operations |
1000 cycles |
|
Making limits |
Limiting making capacity (inductive) |
300 W at L/R = 40 ms for DC or p.f. = 0.4 for AC |
Make and carry (resistive) for 3.0 s |
15 A (3 s On, 15 Off) |
|
Make and carry (resistive) for 0.5 s |
30 A (0.5 s On, 15 s Off) |
|
Breaking limits |
Limiting breaking capacity ≤48 V |
1 A at L/R = 40 ms for DC or p.f. = 0.4 for AC |
Limiting breaking capacity 110 V |
0.25 A at L/R = 40 ms for DC or p.f. = 0.4 for AC |
|
Limiting breaking capacity 220 V |
0.15 A at L/R = 40 ms for DC or p.f. = 0.4 for AC |
|
Minimum contact load |
100 mA |
Description |
Value |
|
---|---|---|
Rated voltage |
250 V AC/DC |
|
Continuous contact carry current |
5 A |
|
Mechanical endurance |
Unloaded operation |
10000 cycles |
Electrical endurance |
Closing operations |
1000 cycles |
Opening operations |
1000 cycles |
|
Making limits |
Limiting making capacity (inductive) |
300 W at L/R = 40 ms for DC or p.f. = 0.4 for AC |
Make and carry (resistive) for 3.0 s |
10 A (3 s On, 15 Off) |
|
Make and carry (resistive) for 0.5 s |
15 A (0.5 s On, 15 s Off) |
|
Breaking limits |
Limiting breaking capacity ≤48 V |
1 A at L/R = 40 ms for DC or p.f. = 0.4 for AC |
Limiting breaking capacity 110 V |
0.25 A at L/R = 40 ms for DC or p.f. = 0.4 for AC |
|
Limiting breaking capacity 220 V |
0.15 A at L/R = 40 ms for DC or p.f. = 0.4 for AC |
|
Minimum contact load |
10 mA |
Description |
Value |
|
---|---|---|
Rated voltage |
250 V AC/DC |
|
Continuous contact carry current |
8 A |
|
Mechanical endurance |
Unloaded operation |
10000 cycles |
Electrical endurance |
Closing operations |
1000 cycles |
Opening operations |
1000 cycles |
|
Making limits |
Limiting making capacity (inductive) |
1000 W at L/R = 40 ms for DC or p.f. = 0.4 for AC |
Make and carry (resistive) for 3.0 s |
15 A (3 s On, 15 Off) |
|
Make and carry (resistive) for 0.5 s |
30 A (0.5 s On, 15 s Off) |
|
Breaking limits |
Limiting breaking capacity ≤48 V (inductive), two contacts connected in series |
5 A at L/R = 40 ms for DC or p.f. = 0.4 for AC |
Limiting breaking capacity 110 V (inductive), two contacts connected in series |
3 A at L/R = 40 ms for DC or p.f. = 0.4 for AC |
|
Limiting breaking capacity 220 V (inductive), two contacts connected in series |
1 A at L/R = 40 ms for DC or p.f. = 0.4 for AC |
|
Minimum contact load |
100 mA |
Type |
Location |
Connector |
---|---|---|
RS-485 |
Rear |
1=B, 2=A, 3=GND, 4=capacitive shield |
Type |
Location |
Connector |
Rate |
---|---|---|---|
USB, micro B |
Front |
USB 1.x / USB 2.0 compatible |
240 Mbits/s (max.) |
Cable |
Protocol |
Location |
Rate |
---|---|---|---|
Standard Ethernet CAT 5 STP cable with RJ-45 connector (shielded) |
TCP/IP |
Rear |
100 Mbits/s |
Description |
Value |
---|---|
Normal service temperature range of the lens | -40...+100ºC |
Maximum service temperature range of the lens, max. 1 hour | +140ºC |
Minimum permissible bending radius of the connection fiber | 100 mm |
Technical specification of the ARC module: | |
ARC detection | >30 μs |
ARC detection range (threshold setting) | >25 dB |
Fiber break detection (heartbeat) | 3 s |
Description |
Value |
---|---|
Front side |
IP 54 |
Left and right side |
IP 20 |
Top and bottom |
IP 20 |
Case inside 2 |
IP 20 |
Description |
Value |
---|---|
Operating temperature range |
-40...+70ºC UL:+55ºC |
Short-time service temperature range |
-40...+85ºC |
Relative humidity |
5...95% (EN60255) |
Atmospheric pressure |
86...106 kPa (test reference/EN60255) |
Altitude |
<2000 m (EN60255) |
Transport and storage temperature range |
-40...+85ºC |