The operate times for the standard overvoltage IDMT curves are defined with the coefficients A, B, C, D and E.

The inverse operate time can be calculated with the formula:
Figure 1. Equation
image/svg+xml
t [s]Operate time in seconds
UMeasured voltage
U>Set value of Start value
kSet value of Time multiplier
Table 1. Curve coefficients for the standard overvoltage IDMT curves
Curve name A B C D E
(17) Inverse Curve A 1 1 0 0 1
(18) Inverse Curve B 480 32 0.5 0.035 2
(19) Inverse Curve C 480 32 0.5 0.035 3
Figure 2. Inverse curve A characteristic of overvoltage protection
Figure 3. Inverse curve B characteristic of overvoltage protection
Figure 4. Inverse curve C characteristic of overvoltage protection