| INIT_1 |
BOOLEAN |
0=False |
AR initialization / blocking signal 1 |
| INIT_2 |
BOOLEAN |
0=False |
AR initialization / blocking signal 2 |
| INIT_3 |
BOOLEAN |
0=False |
AR initialization / blocking signal 3 |
| INIT_4 |
BOOLEAN |
0=False |
AR initialization / blocking signal 4 |
| INIT_5 |
BOOLEAN |
0=False |
AR initialization / blocking signal 5 |
| INIT_6 |
BOOLEAN |
0=False |
AR initialization / blocking signal 6 |
| DEL_INIT_2 |
BOOLEAN |
0=False |
Delayed AR initialization / blocking signal 2 |
| DEL_INIT_3 |
BOOLEAN |
0=False |
Delayed AR initialization / blocking signal 3 |
| DEL_INIT_4 |
BOOLEAN |
0=False |
Delayed AR initialization / blocking signal 4 |
| BLK_RECL_T |
BOOLEAN |
0=False |
Blocks and resets reclose time |
| BLK_RCLM_T |
BOOLEAN |
0=False |
Blocks and resets reclaim time |
| BLK_THERM |
BOOLEAN |
0=False |
Blocks and holds the reclose shot from the thermal overload |
| CB_POS |
BOOLEAN |
0=False |
Circuit breaker position input |
| CB_READY |
BOOLEAN |
1=True |
Circuit breaker status signal |
| INC_SHOTP |
BOOLEAN |
0=False |
A zone sequence coordination signal |
| INHIBIT_RECL |
BOOLEAN |
0=False |
Interrupts and inhibits reclosing sequence |
| RECL_ON |
BOOLEAN |
0=False |
Level sensitive signal for allowing (high) / not allowing (low) reclosing |
| SYNC |
BOOLEAN |
0=False |
Synchronizing check fulfilled |