Parameter |
Values (Range) |
Unit |
Step |
Default |
Description |
---|---|---|---|---|---|
Start value |
0.010...5.000 |
xIn |
0.005 |
0.010 |
Start value |
Start value Mult |
0.8...10.0 |
0.1 |
1 |
Multiplier for scaling the start value |
|
Directional mode |
1=Non-directional 2=Forward 3=Reverse |
2=Forward |
Directional mode |
||
Time multiplier |
0.05...15.00 |
0.01 |
1.00 |
Time multiplier in IEC/ANSI IDMT curves |
|
Operating curve type |
1=ANSI Ext. inv. 2=ANSI Very inv. 3=ANSI Norm. inv. . 4=ANSI Mod. inv. 5=ANSI Def. Time 6=L.T.E. inv. 7=L.T.V. inv. 8=L.T. inv. 9=IEC Norm. inv. 10=IEC Very inv. 11=IEC inv. 12=IEC Ext. inv. 13=IEC S.T. inv. 14=IEC L.T. inv. 15=IEC Def. Time 17=Programmable 18=RI type 19=RD type |
15=IEC Def. Time |
Selection of time delay curve type |
||
Operate delay time |
50...300000 |
ms |
10 |
50 |
Operate delay time |
Characteristic angle |
-179...180 |
deg |
1 |
-90 |
Characteristic angle |
Max forward angle |
0...180 |
deg |
1 |
80 |
Maximum phase angle in forward direction |
Max reverse angle |
0...180 |
deg |
1 |
80 |
Maximum phase angle in reverse direction |
Min forward angle |
0...180 |
deg |
1 |
80 |
Minimum phase angle in forward direction |
Min reverse angle |
0...180 |
deg |
1 |
80 |
Minimum phase angle in reverse direction |
Voltage start value |
0.010...1.000 |
xUn |
0.001 |
0.010 |
Voltage start value |
Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Operation |
1=on 5=off |
1=on | Operation Off / On | ||
Curve parameter A | 0.0086...120.0000 | 0.0001 | 28.2000 | Parameter A for customer programmable curve | |
Curve parameter B | 0.0000...0.7120 | 0.0001 | 0.1217 | Parameter B for customer programmable curve | |
Curve parameter C | 0.02...2.00 | 0.01 | 2.00 | Parameter C for customer programmable curve | |
Curve parameter D | 0.46...30.00 | 0.01 | 29.10 | Parameter D for customer programmable curve | |
Curve parameter E | 0.0...1.0 | 0.1 | 1.0 | Parameter E for customer programmable curve |
Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Reset delay time | 0...60000 | ms | 1 | 20 | Reset delay time |
Minimum operate time | 50...60000 | ms | 1 | 50 | Minimum operate time for IDMT curves |
Allow Non Dir |
0=False 1=True |
0=False |
Allows prot activation as non-dir when dir info is invalid | ||
Measurement mode |
1=RMS 2=DFT 3=Peak-to-Peak |
2=DFT |
Selects used measurement mode | ||
Min operate current | 0.5...1.00.0 | %In | 0.001 | 0.005 | Minimum operating current |
Min operate voltage | 1.0...100.0 | %Un | 0.01 | 0.01 | Minimum operating voltage |
Correction angle | 0.0...10.0 | deg | 0.1 | 0.0 | Characteristic correction angle in IoCos and IoSin mode |
Pol reversal |
0=False 1=True |
0=False |
Rotate polarizing quantity | ||
Pol quantity |
3=Zero seq. volt. 4=Neg. seq. volt. |
3=Zero seq. volt. |
Reference quantity used to determine fault direction |
Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Start value | 0.10...40.00 | xIn | 0.01 | 0.10 | Start value |
Start value Mult | 0.8...10.0 | 0.1 | 1.0 | Multiplier for scaling the start value | |
Directional mode |
1=Non-directional 2=Forward 3=Reverse |
2=Forward | Directional mode | ||
Time multiplier | 0.05...15.00 | 0.01 | 1.00 | Time multiplier in IEC/ANSI IDMT curves | |
Operating curve type |
1=ANSI Ext. inv. 3=ANSI Norm. inv. 5=ANSI Def. Time 15=IEC Def. Time 17=Programmable |
15=IEC Def. Time | Selection of time delay curve type | ||
Operate delay time | 40...300000 | ms | 10 | 40 | Operate delay time |
Characteristic angle | -179...180 | deg | 1 | -90 | Characteristic angle |
Max forward angle | 0...180 | deg | 1 | 80 | Maximum phase angle in forward direction |
Max reverse angle | 0...180 | deg | 1 | 80 | Maximum phase angle in reverse direction |
Min forward angle | 0...180 | deg | 1 | 80 | Minimum phase angle in forward direction |
Min reverse angle | 0...180 | deg | 1 | 80 | Minimum phase angle in reverse direction |
Voltage start value | 0.010...1.000 | xUn | 0.001 | 0.010 | Voltage start value |
Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Type of reset curve |
1=Immediate 2=Def time reset 3=Inverse reset |
1=Immediate | Selection of reset curve type | ||
Operation mode |
1=Phase angle 2=IoSin 3=IoCos 4=Phase angle 80 5=Phase angle 88 |
1=Phase angle | Operation criteria | ||
Enable voltage limit |
0=False 1=True |
1=True | Enable voltage limit |
Parameter |
Values (Range) |
Unit |
Step |
Default |
Description |
---|---|---|---|---|---|
Operation |
1=on 5=off |
1=on |
Operation Off / On |
||
Curve parameter A |
0.0086...120.0000 |
0.0001 |
28.2000 |
Parameter A for customer programmable curve |
|
Curve parameter B |
0.0000...0.7120 |
0.0001 |
0.1217 |
Parameter B for customer programmable curve |
|
Curve parameter C |
0.02...2.00 |
0.01 |
2.00 |
Parameter C for customer programmable curve |
|
Curve parameter D |
0.46...30.00 |
0.01 |
29.10 |
Parameter D for customer programmable curve |
|
Curve parameter E |
0.0...1.0 |
0.1 |
1.0 |
Parameter E for customer programmable curve |
Parameter |
Values (Range) |
Unit |
Step |
Default |
Description |
---|---|---|---|---|---|
Reset delay time |
0...60000 |
ms |
1 |
20 |
Reset delay time |
Minimum operate time |
40...60000 |
ms |
1 |
40 |
Minimum operate time for IDMT curves |
Allow Non Dir |
0=False 1=True |
0=False |
Allows prot activation as non-dir when dir info is invalid |
||
Measurement mode |
1=RMS 2=DFT 3=Peak-to-Peak |
2=DFT |
Selects used measurement mode |
||
Min operate current |
0.005...1.000 |
xIn |
0.001 |
0.005 |
Minimum operating current |
Min operate voltage |
0.01...1.00 |
xUn |
0.01 |
0.01 |
Minimum operating voltage |
Correction angle |
0.0...10.0 |
deg |
0.1 |
0.0 |
Characteristic correction angle in IoCos and IoSin mode |
Pol reversal |
0=False 1=True |
0=False |
Rotate polarizing quantity |
||
Pol quantity |
3=Zero seq. volt. 4=Neg. seq. volt. |
3=Zero seq. volt. |
Reference quantity used to determine fault direction |