Table 1. PHPTUV Group settings (Basic)

Parameter

Values (Range)

Unit

Step

Default

Description

Operating curve type

5=ANSI Def. Time

15=IEC Def. Time

21=Inv. Curve A

22=Inv. Curve B

23=Programmable

15=IEC Def. Time

Selection of time delay curve type

Time multiplier

0.05...15.00

0.01

1.00

Time multiplier in IEC/ANSI IDMT curves

Start value

0.05...1.20

xUn

0.01

0.90

Start value

Operate delay time

60...300000

ms

10

60

Operate delay time

Table 2. PHPTUV Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Type of reset curve

1=Immediate

2=Def time reset

1=Immediate Selection of reset curve type
Type of time reset

1=Freeze Op timer

2=Decrease Op timer

1=Freeze Op timer Selection of time reset

Table 3. PHPTUV Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation

1=on

5=off

1=on Operation Off / On
Num of start phases

1=1 out of 3

2=2 out of 3

3=3 out of 3

1=1 out of 3 Number of phases required for operate activation
Curve parameter A 0.005...200.000 0.001 1.000 Parameter A for customer programmable curve
Curve parameter B 0.50...100.00 0.01 1.00 Parameter B for customer programmable curve
Curve parameter C 0.0...1.0 0.1 0.0 Parameter C for customer programmable curve
Curve parameter D 0.000...60.000 0.001 0.000 Parameter D for customer programmable curve
Curve parameter E 0.000...3.000 0.001 1.000 Parameter E for customer programmable curve
Voltage selection

1=phase-to-earth

2=phase-to-phase

2=phase-to-phase Parameter to select phase or phase-to-phase voltages

Table 4. PHPTUV Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Minimum operate time 60...60000 ms 1 60 Minimum operate time for IDMT curves
Reset delay time 0...60000 ms 1 20 Reset delay time
Curve Sat Relative 0.0...10.0 0.1 0.0 Tuning parameter to avoid curve discontinuities
Voltage block value 0.05...1.00 xUn 0.01 0.20 Low level blocking for undervoltage mode
Enable block value

0=False

1=True

1=True Enable internal blocking
Relative hysteresis 1.0...5.0 % 0.1 4.0 Relative hysteresis for operation