Settings - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - IEC - ANSI - 12.12.2023

REX610 Technical Manual

Table 1. DPHLPDOC Group settings (Basic)

Parameter

Values (Range)

Unit

Step

Default

Description

Operating curve type

1=ANSI Ext. inv.

2=ANSI Very inv.

3=ANSI Norm. inv. .

4=ANSI Mod. inv.

5=ANSI Def. Time .

6=L.T.E. inv.

7=L.T.V. inv.

8=L.T. inv..

9=IEC Norm. inv.

10=IEC Very inv.

11=IEC inv.

12=IEC Ext. inv.

13=IEC S.T. inv.

14=IEC L.T. inv.

15=IEC Def. Time

17=Programmable

18=RI type

19=RD type

15=IEC Def. Time

Selection of time delay curve type

Time multiplier

0.05...15.00

0.01

1

Time multiplier in IEC/ANSI IDMT curves

Start value

0.05...5.00

xIn

0.01

0.05

Start value

Start value Mult

0.8...10.0

0.1

1

Multiplier for scaling the start value

Operate delay time

40...300000

ms

10

40

Operate delay time

Directional mode

1=Non-directional

2=Forward

3=Reverse

2=Forward

Directional mode

Characteristic angle

-179...180

deg

1

60

Characteristic angle

Max forward angle

0...90

deg

1

80

Maximum phase angle in forward direction

Max reverse angle

0...90

deg

1

80

Maximum phase angle in reverse direction

Min forward angle

0...90

deg

1

80

Minimum phase angle in forward direction

Min reverse angle

0...90

deg

1

80

Minimum phase angle in reverse direction

Table 2. DPHLPDOC Group settings (Advanced)

Parameter

Values (Range)

Unit

Step

Default

Description

Type of reset curve

1=Immediate

2=Def time reset

3=Inverse reset

1=Immediate

Selection of reset curve type

Voltage Mem time

0...3000

ms

1

40

Voltage memory time

Pol quantity

1=Self pol

4=Neg. seq. volt. .

5=Cross pol

7=Pos. seq. volt.

5=Cross pol

Reference quantity used to determine fault direction

Table 3. DPHLPDOC Non group settings (Basic)

Parameter

Values (Range)

Unit

Step

Default

Description

Operation

1=on

5=off

1=on

Operation Off / On

Num of start phases

1=1 out of 3

2=2 out of 3

3=3 out of 3

1=1 out of 3

Number of phases required for operate activation

Curve parameter A

0.0086...120.0000

0.0001

28.2000

Parameter A for customer programmable curve

Curve parameter B

0.0000...0.7120

0.0001

0.1217

Parameter B for customer programmable curve

Curve parameter C

0.02...2.00

0.01

2.00

Parameter C for customer programmable curve

Curve parameter D

0.46...30.00

0.01

29.10

Parameter D for customer programmable curve

Curve parameter E

0.0...1.0

0.1

1.0

Parameter E for customer programmable curve

Table 4. DPHLPDOC Non group settings (Advanced)

Parameter

Values (Range)

Unit

Step

Default

Description

Measurement mode

1=RMS

2=DFT

3=Peak-to-Peak

2=DFT

Selects used measurement mode

Minimum operate time

20...60000

ms

1

20

Minimum operate time for IDMT curves

Reset delay time

0...60000

ms

1

20

Reset delay time

Allow Non Dir

0=False

1=True

0=False

Allows prot activation as non-dir when dir info is invalid

Min operate current

0.01...1.00

xIn

0.01

0.01

Minimum operating current

Min operate voltage

0.01...1.00

xUn

0.01

0.01

Minimum operating voltage

Table 5. DPHHPDOC Group settings (Basic)

Parameter

Values (Range)

Unit

Step

Default

Description

Start value

0.10...40.00

xIn

0.01

0.1

Start value

Start value Mult

0.8...10.0

0.1

1

Multiplier for scaling the start value

Directional mode

1=Non-directional

2=Forward

3=Reverse

2=Forward

Directional mode

Time multiplier

0.05...15.00

0.01

1

Time multiplier in IEC/ANSI IDMT curves

Operating curve type

1=ANSI Ext. inv.

3=ANSI Norm. inv.

5=ANSI Def. Time

9=IEC Norm. inv.

10=IEC Very inv.

12=IEC Ext. inv.

15=IEC Def. Time

17=Programmable

15=IEC Def. Time

Selection of time delay curve type

Operate delay time

40...300000

ms

10

40

Operate delay time

Characteristic angle

-179...180

deg

1

60

Characteristic angle

Max forward angle

0...90

deg

1

80

Maximum phase angle in forward direction

Max reverse angle

0...90

deg

1

80

Maximum phase angle in reverse direction

Min forward angle

0...90

deg

1

80

Minimum phase angle in forward direction

Min reverse angle

0...90

deg

1

80

Minimum phase angle in reverse direction

Table 6. DPHHPDOC Group settings (Advanced)

Parameter

Values (Range)

Unit

Step

Default

Description

Type of reset curve

1=Immediate

2=Def time reset

3=Inverse reset

1=Immediate

Selection of reset curve type

Voltage Mem time

0...3000

ms

1

40

Voltage memory time

Pol quantity

1=Self pol

4=Neg. seq. volt.

5=Cross pol

7=Pos. seq. volt.

5=Cross pol

Reference quantity used to determine fault direction

Table 7. DPHHPDOC Non group settings (Basic)

Parameter

Values (Range)

Unit

Step

Default

Description

Operation

1=on

5=off

1=on

Operation Off / On

Curve parameter A

0.0086...120.0000

0.0001

28.2000

Parameter A for customer programmable curve

Curve parameter B

0.0000...0.7120

0.0001

0.1217

Parameter B for customer programmable curve

Curve parameter C

0.02...2.00

0.01

2.00

Parameter C for customer programmable curve

Curve parameter D

0.46...30.00

0.01

29.10

Parameter D for customer programmable curve

Curve parameter E

0.0...1.0

0.1

1.0

Parameter E for customer programmable curve

Num of start phases

1=1 out of 3

2=2 out of 3

3=3 out of 3

1=1 out of 3

Number of phases required for operate activation

Table 8. DPHHPDOC Non group settings (Advanced)

Parameter

Values (Range)

Unit

Step

Default

Description

Reset delay time

0...60000

ms

1

20

Reset delay time

Minimum operate time

20...60000

ms

1

20

Minimum operate time for IDMT curves

Allow Non Dir

0=False

1=True

0=False

Allows prot activation as non-dir when dir info is invalid

Measurement mode

1=RMS

2=DFT

3=Peak-to-Peak

2=DFT

Selects used measurement mode

Min operate current

0.01...1.00

xIn

0.01

0.01

Minimum operating current

Min operate voltage

0.01...1.00

xUn

0.01

0.01

Minimum operating voltage