Parameter |
Values (Range) |
Unit |
Step |
Default |
Description |
---|---|---|---|---|---|
Num of phases |
1=1 out of 3 2=2 out of 3 3=3 out of 3 |
1=1 out of 3 |
Number of phases required by limit supervision |
||
V high high limit |
0.00...4.00 |
xUn |
0.01 |
1.40 |
High alarm voltage limit |
V high limit |
0.00...4.00 |
xUn |
0.01 |
1.20 |
High warning voltage limit |
V low limit |
0.00...4.00 |
xUn |
0.01 |
0.00 |
Low warning voltage limit |
V low low limit |
0.00...4.00 |
xUn |
0.01 |
0.00 |
Low alarm voltage limit |
V deadband |
100...100000 |
1 |
10000 |
Deadband configuration value for integral calculation. (percentage of difference between min and max as 0,001 % s) |
|
Operation |
1=on 5=off |
1=on |
Operation Off / On |
Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Measurement mode |
1=RMS 2=DFT |
2=DFT | Selects used measurement mode | ||
On delay time | 0...1800000 | ms | 100 | 0 | Delay the activation of the alarm and warning outputs |
Off delay time | 0...1800000 | ms | 100 | 0 | Delay the deactivation of the alarm and warning outputs |