Settings - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - IEC - ANSI - 03.05.2023

REX610 Technical Manual

Table 1. CCSPVC Non group settings (Basic)

Parameter

Values (Range)

Unit

Step

Default

Description

Start value

0.05...0.20

xIn

0.01

0.05

Minimum operate current differential level

Operation

1=on 5=off

1=on

Operation On / Off

Table 2. CCSPVC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Max operate current 1.00...5.00 xIn 0.01 1.50 Block of the function at high phase current